Inspection History: SIGN ELECTRIC
Permit Number - T11OT01158
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2013 | SIGN ELECTRIC | Approved | MET THE CONTRACTORS REPRESENTATIVE ON SITE AND INSPECTED THE SIGN. THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED AND THE SIGN WILL BE APPROVED AT THIS TIME. AN OPENNING IN THE TOP OF THE SIGN BOX WAS NOTED AND REPAIRED PRIOR TO MY LEAVING THE SITE. I DISCUSSED THE CURRENT CONDITIONS, AND LOOKED OVER FIELD PHOTOS WITH RAY MAJUTA PRIOR TO SIGNING OFF THIS INSPECTION. THEN I CONTACTED RAY FROM SUNRAY SIGNS INC. AND ADVISED HIM TO PLACE ADDITIONAL CLEARANCE SUPPORTS UNDERNEATH THE GTO WIRES AND PLACE GROMMETS AROUND ONE OF THE WALL PENETRATIONS PRIOR TO CLOSING THE BOX. |
|
07/03/2013 | SIGN ELECTRIC | Approved | ALL PREVIOOUS COMMENTS HAVE BEEN ADDRESSED AT THIS TIME. | |
07/02/2013 | SIGN ELECTRIC | Not ready for Inspection | ||
01/23/2012 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TIGHTEN HIGH VOLTAGE TERMINATIONS 2) SPACE AND INSTALL GTO CABLES FROM GROUNDED SURFACE 3) TOP ACCESS ENTERING COVER NOT ACCESSIBLE DUE TO RACEWAY 4) COULD NOT VERIFY RACEWAY BONDING |
|
01/18/2012 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SIGN CONTRACTOR NEEDS TO BE ON SITE 2) RESCHEDULE INSPECTION |