Permit: T11OT00100

Parcel: 12602006A


Addresses:

4628 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/27/2011 FIRE - FINAL Approved
01/18/2011 FIRE - FINAL Denied Not approved 01/18/11
1.) Need an emergency back-up light to illuminate front exit door.
2.) Emergency back-up light over secondary exit door is burnt out.
3.) Exit doors must be visible from any portion of the building if they are not ,"Directional "exit signs must be provided.
4.) All exit doors must lead to a public way. All secondary exit doors must be equipped with panic hardware. Exterior gate door is a secondary exit.
5.) Extention cords are for temporary use only and not to be a substitute for permanent wiring.
6.) Cover opening in wall next to ceiling.
7.) Secure all open-end wiring (exposed wiring)
8.) All permanent wiring must must comply with the electrical code. (ROMEX wiring leading out exterior north wall, storage room area)
9.) Lable circut breakers in electrical panel.
10.) Lable the door where main breaker is located "ELECTRICAL"
(small shed-like room located outside)
11.) Maintain clear an unobstructed path for exit access, exit and exit discharge areas.