Permit: T11OT00040

Parcel: 112062340


Addresses:

2512 N CAMPBELL AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T11OT00040

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2011 FIRE - FINAL Approved
01/13/2011 FIRE - FINAL Denied Not approved 1/13/11
1.) Provide a "NOT AN EXIT" sign for front door south end.
2.) Replace ceiling tile, small closet.
3.) Cover/secure open end wiring, ceiling, small closet.
4.) Maintain a minimum of 18 inches of clearance from any fire sprinkler head
5.) Exit pathway can not pass through a storage area
6.) Must maintain a clear area in front of any exit door or pathway
7.) All exterior doors must swing in the direction of egress travel.
8.) Emergency back-up lighting is required for all required exit doors.