Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T11OT00040
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2011 | FIRE - FINAL | Approved | ||
| 01/13/2011 | FIRE - FINAL | Denied | Not approved 1/13/11 1.) Provide a "NOT AN EXIT" sign for front door south end. 2.) Replace ceiling tile, small closet. 3.) Cover/secure open end wiring, ceiling, small closet. 4.) Maintain a minimum of 18 inches of clearance from any fire sprinkler head 5.) Exit pathway can not pass through a storage area 6.) Must maintain a clear area in front of any exit door or pathway 7.) All exterior doors must swing in the direction of egress travel. 8.) Emergency back-up lighting is required for all required exit doors. |