Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2011 | FIRE - FINAL | Denied | 1. Need to add sprinkler coverage in store room by sprinkler riser, you will need approved plans and permits for this work. 2. Repair or replace ceiling tile around sprinkler riser 3. Outlet cover plates missing in that needs sprinkler coverage. 4. Need light switch install by entry door to turn lights on when entering a room. (This is for room that needs sprinkler coverage.) 5. Need up to date sprinkler report. |
|
| 01/10/2011 | FIRE - FINAL | Denied | No one on site - locked call in again |