Permit: T11OT00013

Parcel: 12213149B


Addresses:

1526 N BRYANT AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/08/2011 FIRE - FINAL Approved
03/30/2011 FIRE - FINAL Correction Required 1526 & 1528 APPROVED
1530 DENIED - NO SPRINKLER COVERAGE IN FURNACE ROOM/CLOSET.
03/08/2011 FIRE - FINAL Denied 1) Need sprinkler final.
2) Need sprinkler coverage in furnace rooms.
3) Need emergency lighting units.
01/26/2011 FIRE - FINAL Denied 1) Show proof from a licensed sprinkler contractor that you have proper sprinkler coverage.
2) All three addresses shall be posted on the building and individual doors. Go to development services (addressing) if you wish to make it one address.
3) Sprinkler heads in kitchen obstructed by cabinets.
4) No sprinkler coverage in storage rooms, south of kitchen.
5) Sprinkler coverage required in furnace rooms.
6) Emergency lighting units required. Must illuminate required exits and bedroom halls.