Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE ELECTRIC DISCONNECT 2) PROVIDE A STAND PIPE IN CONDENSATE DRAIN VENT 3) PROVIDE A HOSE CLAMP ON PUMP HOSE 4) I.D. CIRCUIT BREAKER 5) PROVIDE RED WOOD OR PRESSURE TREATED BLOCKS FOR REFER LINE SET-SECURE TO BLOCKS 6) BLOCK AND CLAMP DRAIN LINE ON ROOF EVERY 6' |
|
| 04/03/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |