Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/16/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/15/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/14/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE GAS PRESSURE TEST ON NEW PIPING TO FURNACE
2) PROVIDE MINIMUM R-8 FLEX DUCT IN VENTED ATTIC
3) ALL CANS IN ATTIC ARE TO BE INSULATED R-8
4) PROVIDE MINIMUM 1" CLEARANCE TO COMBUSTIBLE MATERIALS FROM B-VENT
5) CEILING BOOTS NOT PROPERLY INSTALLED
6) THIS IS A NEW INSTALLATION REVISE PERMIT TO REFLECT AS SUCH, INCLUDE GAS PIPING, ELECTRIC AND ALSO PROVIDE ISOMETRIC PIPING DIAGRAM AND LOAD CALC FOR UNIT WEIGHT
NOTE:
THIS PERMIT WAS INTENDED TO INCLUDE GAS PRESSURE TEST FOR RECONNECT, PLEASE ADD TO PERMIT