Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11ME00305
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/04/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT STILL NOT INSTALLED CORRECTLY 2) YOU CANNOT MIX FITTINGS FROM AMERIVENT WITH FITTINGS FROM METAL FAB, THE CONNECTIONS DO NOT MATCH 3) THE ELBOW CONNECTED INTO THE VENT AT WALL OPENING IS NOT FITTED INTO THE VENT CORRECTLY 4) YOU CANNOT USE FOIL TAPE AS A BANDAID BECAUSE YOUR FITTINGS MUST SNAP TOGETHER AS THEY WERE DESIGNED TO DO 5) THE AMERIVENT ELBOW IS UN-NECESSARY, YOU CAN STILL USE SINGLE WALL AT THAT POINT |
|
11/07/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) A/C NOT COMPLETE 2) DUCT NOT COMPLETE 3) FLUE PIPE INCORRECTLY INSTALLED 4) PROVIDE SEDIMENT TRAP ON GAS LINE 5) ELECTRICAL NOT PROPERLY INSTALLED |