Permit: T11ME00269

Parcel: 133260680


Addresses:

8102 E 5TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/12/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/11/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE 6" CLEARANCE FROM PVC AT VENT CONNECTOR OR USE DBL WALL PIPE
2) TAPE OR GLUE SEAMS ON ARMAFLEX IN CLOSET
3) EXTEND VENT ON CONDENSATE TRAP ABOVE DRAIN PAN
4) REPAIR STRANDED WIRE IN DISCONNECT