Permit: T11ME00255

Parcel: 127040590


Addresses:

5044 E 1ST ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/21/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/19/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP IN CONDENSATE DRAIN LINE
2) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND
3) SUPPORT EVERY 4' AND PAINT WITH LATEX PAINT
4) SECURE THE ANGLE IRON STAND TO THE STRUCTURE
5) COVER ALL OF THE CANVAS CONNECTORS WITH A SUN SHIELD
09/15/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) PROVIDE ACCESS TO THE ROOF