Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/14/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 2) NO DUCT TAPE ALLOWED OUTDOORS 3) IS USING TAPE TO WRAP LINE SET, BE SURE TO USE UL OR UPC LISTED TAPE. 10 MIL TAPE IS OK 4) ONE FUSE IS 60 AMP, 40 IS MAXIMUM 5) TAPE OR GLUE SEAMS ON ARMAFLEX |