Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/03/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANDUITS NOT TO BE USED AS DUCT HANGERS 2) WHEN TYING 2 CONDENSATE LINES TOGETHER, SIZE OF PIPE MUST INCREASE TO 1" MININUM 3) DUCT NOT TO BE SUPPORTED BY CONDUIT 4) SEAL PENETRATIONS WHERE CONDUIT TO CONDENSORS EXISTS BLDG |