Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/08/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS FLEX CONNECTOR CANNOT EXCEED 3' IN LENGTH 2) B-VENT THRU ROOF IS UPSIDE DOWN, DOES NOT HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES, DOE NOT HAVE AN APPROVED CAP. REMOVE THE SINGLE WALL 90 DEGREES. ELBOW SPLICED INTO DBL WALL IN ATTIC 3) INSULATE ALL BARE SHEET METAL DUCT, FITTINGS AND PLENIUMS IN ATTIC WITH MINIMUM R8 INSULATION. PROPERLY SEAL RETURN DUCT CONNECTION TO PLENIUM |
|
| 07/06/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THERE IS NO ACCESS INTO THE ATTIC |
|
| 06/22/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MINIMUM ACCESS IS 20" X 30" 2) PROVIDE PLATFORM TO UNIT TO COMPLETE INSPECTION 3) SINGLE WALL FLUE PIPE NOT TO BE USED IN ATTIC SPACE, PROVIDE B-VENT ONLY |