Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/20/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DUCT IS TO BE INSULATED, INSULATION IS TO HAVE A VAPOR BARRIER 2) ALL DUCT JOINTS ARE TO BE SEALED 3) LINED DUCT ONLY HAS 1/2" LINER, THIS DOES NOT MEET MINIMUM REQUIREMENTS OF R-4.2 4) PROVIDE ROOF LOAD CALC FOR UNIT 5) UNIT NOT LEVEL 6) PROVIDE SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT |
|
| 06/16/2011 | MECHANICAL - FINAL | Cancelled | CANCELLED PER CONTRACTOR MELINDA #881-1207 | |
| 06/16/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |