Permit: T11ME00160

Parcel: 130152490


Addresses:

4558 E 26TH ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/23/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
06/20/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) DUCT IS TO BE INSULATED, INSULATION IS TO HAVE A VAPOR BARRIER
2) ALL DUCT JOINTS ARE TO BE SEALED
3) LINED DUCT ONLY HAS 1/2" LINER, THIS DOES NOT MEET MINIMUM REQUIREMENTS OF R-4.2
4) PROVIDE ROOF LOAD CALC FOR UNIT
5) UNIT NOT LEVEL
6) PROVIDE SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT
06/16/2011 MECHANICAL - FINAL Cancelled CANCELLED PER CONTRACTOR MELINDA #881-1207
06/16/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*