Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/17/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WEST FURNACE RELOCATE REFER LINE SET BLOCKING REMOVAL OF WATER HEATER 2) PROVIDE 6" CLEARANCE FROM ARMAFLEX AND VENT CONNECTOR 3) PROVIDE BUSHINGS IN KNOCKOUTS IN EVAP. COIL 4) PROVIDE A HOSE CLAMP AT CONNECTION TO CONDENSATE PUMP 5) EAST FURNACE INSULATE BARE SHEET METAL DUCT ABOVE EVAP. COIL 6) REMOVE ANY DUCT TAPE USED OUTDOORS ON LINE SET AND PROVIDE A PROTECTIVE COATING ON ARMAFLEX 7) TERMINATE CONDENSATE WITHIN 6" OF THE GROUND 8) PROVIDE OUTDOOR FITTINGS ON ELECTRIC CONDUITS 9) PROVIDE ROOF JACKS AT ELECTRIC PENETRATIONS THRU ROOF 10) TAPE ENDS OF WHITE WIRES WITH BLACK TAPE 11) SECURE COPPER DRAIN LINE TO BLOCKS ON ROOF 12) SERVICE RECEPT MUST BE HOT AT ALL TIMES |