Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2017 | MECHANICAL - INTERMEDIATE | Approved | ||
| 03/31/2011 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAIN ON ROOF 2) TERMINATE 3/8" COPPER DRAIN INTO 3/4" WITH A FITTING 3) CONNECT OVER FLOW SENSOR ON CONDENSATE PUMP 4) EXTEND ARMAFLEX TO END OF SUCTION LINE AT COIL 5) TIGHTEN ROMEX CONNECTOR ONTO POWER CORD AT FURNACE 6) LINE SET COPPER RESTING ON KNOCKOUT HOLES AND PROVIDE BUSHINGS |