Permit: T11ME00099

Parcel: 121011020


Addresses:

6132 E HAMPTON ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/01/2017 MECHANICAL - INTERMEDIATE Approved
03/31/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAIN ON ROOF
2) TERMINATE 3/8" COPPER DRAIN INTO 3/4" WITH A FITTING
3) CONNECT OVER FLOW SENSOR ON CONDENSATE PUMP
4) EXTEND ARMAFLEX TO END OF SUCTION LINE AT COIL
5) TIGHTEN ROMEX CONNECTOR ONTO POWER CORD AT FURNACE
6) LINE SET COPPER RESTING ON KNOCKOUT HOLES AND PROVIDE BUSHINGS