Permit: T11ME00070

Parcel: 13309002A


Addresses:

8240 E PIMA ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/11/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/03/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU CANNOT USE THE A/C CIRCUIT TO POWER THE SERVICE RECEPT
2) PROVIDE A BUSHING IN THE DISCONNECT AT CONNECTION TO A/C UNIT THAT ACTUALLY FITS THE KNOCKOUT HOLE
3) MARK THE UNIT DATA PLATE HEAT STRIP INFO AND FUSE ACCORDINGLY