Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11ME00048
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/01/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/22/2011 | MECHANICAL - FINAL | Not ready for Inspection | CONDENSING UNIT OVER FUSED. MAX FUSE SIZE IS 15 AMP. UNIT HAS 30 AMP FUSE COAT LINE SET INSULATION FOR U.V. PROTECTION LINE SET TO BE INSULATED EXTENDING OVER DRAIN PAN AT EVAP COIL AIR HANDLER COVER MISSING SCREWS |
|
08/18/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME AT UNITS A OR B 2) PROVIDE UNIT NUMBER AND CONTACT NUMBER FOR NEXT INSPECTION |