Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT CONNECTOR CRIMPED ENDS NOT FITTED PROPERLY 2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS 3) PROVIDE AN OVERFLOW SENSOR IN SECONDARY DRAIN 4) CONNECT OVERFLOW SENSOR ON PUMP 5) CONDENSATE MUST TERMINATE TO WITHIN 6" OF THE GROUND 6) REPAIR BROKEN CONDUIT AT DISCONNECT ON ROOF 7) PROVIDE A PROTECTIVE COATING EXPOSED ARMAFLEX AT CONDENSOR 8) PROVIDE ACCESS TO ROOF 9) I.D. CIRCUIT BREAKER FOR CONDENSOR |