Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11ME00017
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/24/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/22/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT CONNECTOR CRIMPED ENDS NOT FITTED PROPERLY 2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS 3) PROVIDE AN OVERFLOW SENSOR IN SECONDARY DRAIN 4) CONNECT OVERFLOW SENSOR ON PUMP 5) CONDENSATE MUST TERMINATE TO WITHIN 6" OF THE GROUND 6) REPAIR BROKEN CONDUIT AT DISCONNECT ON ROOF 7) PROVIDE A PROTECTIVE COATING EXPOSED ARMAFLEX AT CONDENSOR 8) PROVIDE ACCESS TO ROOF 9) I.D. CIRCUIT BREAKER FOR CONDENSOR |