Permit: T11ME00011

Parcel: 126070510


Addresses:

201 N ROJEN CT

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/07/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
01/24/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) INSULATE RETURN AIR DUCT IN WATER HEATER CLOSET
2) WATER HEATER VENT CONNECTOR UPSIDE DOWN
3) TERMINATE VENT CONNECTOR INTO THE DBL WALL VENT, NOT OVER THE VENT
4) OK TO USE/OPENING METHOD FOR WATER HEATER COMBUSTION AIR-MUST BE HIGH OPENING