Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 01/24/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) INSULATE RETURN AIR DUCT IN WATER HEATER CLOSET 2) WATER HEATER VENT CONNECTOR UPSIDE DOWN 3) TERMINATE VENT CONNECTOR INTO THE DBL WALL VENT, NOT OVER THE VENT 4) OK TO USE/OPENING METHOD FOR WATER HEATER COMBUSTION AIR-MUST BE HIGH OPENING |