Permit: T11ME00010

Parcel: 110152260


Addresses:

2520 N VAN BUREN AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/17/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/03/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DENIED-
PROVIDE MIN 6" CLEARANCE WHERE ARMAFLEX IS HEAR VENT CONNECTOR.
CONNECT THE OVERFLOW SENSOR OR CONDENSATE PUMP.
PROVIDE A RECPTACLE FOR PUMP AND FURNACE. SRU BOX NOT REQUIRED.
CONDENSATE CANNOT TERMINATE INTO A SEWER VENT.
PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX.
PROVIDE THE REQUIRED STRUCTURAL ROOF DRAWING FOR A/C UNIT ON ROOF.
SECURE THE ELEC DISCONNECT BETTER.
SECURE ANGLE IRON FRAME TO THE ROOF.
PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE AT THE CONDENSOR.
USE ONLY DOUBLE WALL VENT PIPE TO EXTEND VENT ABOVE THE COOLER. NO SINGLE WALL ALLOWED.