Permit: T11ME00009

Parcel: 110150590


Addresses:

5601 E KELSO ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11ME00009

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
02/16/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/07/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
STAND PIPE TO EXTEND ABOVE THE DRAIN PAN INSIDE EVAP. COIL.
NO PVC ALLOWED WITHIN 6" OF FURNANCE VENT. DO NOT USE THE A/C CIRCUIT TO POWER THE SERVICE RECEPTACLE. INSTALL A SEPERATE CIRCUIT.
01/20/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE A STAND PIPE IN VENT ON CONDESATE DRAIN EXTENDED ABOVE DRAIN PAN.
2. PROVIDE A HOSE CLAMP ON CONDENSATE PUMP HOSE
3. PROVIDE MIN 6' CLEARANCE FROM ARMAFLEX AT VENT CONNECTOR + PVC NEAR VENT CONNECTOR.
4. VENT CONNECTOR CRIMPED ENDS INSTALLED UPSIDE DOWN. DONOT USE FOIL TAPE. VENT NOT REQUIRED TO BE SEALED.
5. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMFLEX + REPAIR SMALL SECTION.
6. TERMINATE CONDESATE TO THE GROUND. SUPPORT EVERY 6'
7. PROVIDE THE REQUIRED GFI SERVICE SUPPORT RECEPTACLE ON TGHE ROOF.