Inspection History: MECHANICAL - FINAL
Permit Number - T11ME00009
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/16/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
02/16/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
02/07/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* STAND PIPE TO EXTEND ABOVE THE DRAIN PAN INSIDE EVAP. COIL. NO PVC ALLOWED WITHIN 6" OF FURNANCE VENT. DO NOT USE THE A/C CIRCUIT TO POWER THE SERVICE RECEPTACLE. INSTALL A SEPERATE CIRCUIT. |
|
01/20/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A STAND PIPE IN VENT ON CONDESATE DRAIN EXTENDED ABOVE DRAIN PAN. 2. PROVIDE A HOSE CLAMP ON CONDENSATE PUMP HOSE 3. PROVIDE MIN 6' CLEARANCE FROM ARMAFLEX AT VENT CONNECTOR + PVC NEAR VENT CONNECTOR. 4. VENT CONNECTOR CRIMPED ENDS INSTALLED UPSIDE DOWN. DONOT USE FOIL TAPE. VENT NOT REQUIRED TO BE SEALED. 5. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMFLEX + REPAIR SMALL SECTION. 6. TERMINATE CONDESATE TO THE GROUND. SUPPORT EVERY 6' 7. PROVIDE THE REQUIRED GFI SERVICE SUPPORT RECEPTACLE ON TGHE ROOF. |