Permit: T11ME00006

Parcel: 128150490


Addresses:

5313 E DOUGLAS ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11ME00006

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/13/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LADDER FOR ROOF INSPECTION
06/10/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME
01/13/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE THE REQUIRED ROOF TOP STRUCTURAL DRAWING FOR NEW A/C ON THE ROOF
2) PROVIDE R8 DUCT LINER IN ALL EXPOSED DUCT ON ROOF
3) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND
4) 3/8" I.D. X 24" GAS FLEX NOT ADEQUATE FOR 100,000 BTU
5) RELOCATE DISCONNECT MOUNTED TO SERVICE PANEL
6) INSULATE PLENIUM IN ATTIC WITH R8 INSULATION
7) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF