Permit: T11ME00002

Parcel: 133102300


Addresses:

8421 E BOGOTA PL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11ME00002

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/16/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
03/25/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECT WIRED BACKWARDS, LINE AND LOAD REVERSED
2) SUPPORT PVC EVERY 4' AND PAINT WITH LATEX PAINT
3) ALL EXPOSED DUCT TO BE INSULATED WITH MINIMUM R8
4) PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NE ROOF TOP INSTALLATION. DRAWING PROVIDED IS INCOMPLETE
5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF
6) PROVIDE A SEDIMENT TRAP IN GAS LINE AT CONNECTION TO UNIT
01/04/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ACCESS TO ROOF