Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T11FR01076

Parcel: 124150270


Addresses:

807 S EUCLID AV


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR01076

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2012 VIOL - FIRE PROTECTION SYSTEMS Approved
10/27/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. 3 OS&Y (Outside Stem and Yoke) valves are corroded and are not accessible - shall repair or replace valves and make accessible by remove any storage around the area so inspector can have access at all times.
2. Inspector test valve has no water flow and unable to find 2nd test valve - Shall repair or replace test valve and locate and sign all inspectors test vales.
3. FDC (Fire Department Connection) obstructed - maintain a clear access to FDC at all times (post a sign stating "NO PARKING" KEEP CLEAR)
4. Hanger and Supports detached from building - Shall repair or replace all hangers and supports that are detached from building that are used for the sprinkler system.
5. FDC (Fire Department Connection) Siamese FDC has no sign - shall provide proper signage for the FDC.
6. Fire hose in hose cabinets is outdated - Shall test all hoses in hose cabinets or replace with new hose, this is to be done annually.
7. 350 plus sprinkler heads are over the age of 50 years old - Shall test a sample of heads per NFPA 25 or replace all heads. NOTE: You will need a permit from Tucson Fire Department to do this work.
8. NAC batteries located above offices failed load test - Shall replace batteries.
9. Supervisory switch for system control valves in docks where not tested - Shall have all supervisory switches tested.