Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01068
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
09/22/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Replace missing FDC caps Need 5 year check valve inspection completed Repair or replace handle on main control valve Repair or replace water motor gong Re-install insulation in warehouse Correct sprinkler head by west stairwell |