Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01067
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All reports and repairs done. | |
09/21/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Need 5 year check valve inspection. In room 328 sprinkler head is 175 deg should be 155 deg head. 3rd floor trash rom heads has corrosion - change out to find leak. Need to repair or replace check valve its leaking. |