Case: T11FR01067

Parcel: 137341410


Addresses:

6251 S COMMERCE CT

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
10/27/2011 VIOL - FIRE PROTECTION SYSTEMS Approved All reports and repairs done.
09/21/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required Need 5 year check valve inspection.
In room 328 sprinkler head is 175 deg should be 155 deg head.
3rd floor trash rom heads has corrosion - change out to find leak.
Need to repair or replace check valve its leaking.