Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01065
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 10/25/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Shed moved out, but still needs to cut back or remove cover walkway over front entrance door. | |
| 09/27/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Received report from United Fire 5 year was done on 09/25/2009. | |
| 09/21/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Back of bell leaks when water is running. - Need to repair bell 2. No coverage in shed at the southwest corner of the warehouse. - Shall add sprinkler coverage or remove shed. 3. No coverage in shed at entrance door. - Remove shed or make less then 4 feet wide or add sprinjkler coverage. |
|
| 09/21/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Need a 5 year check valve inspection done. |