Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01062
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Wildat called stated they did get all repairs done | |
| 09/15/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Unable to perform 5 year check valve inspections to due to main control valves can not be fully closed. - Shall repair or replace main control valves and perform 5 year check valve inspection. 2. Gauges on risers are out dated - shall recalibrate or replace gauges on both risers. |