Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01051
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Building 1 1. Gauges shall be recalibrated or replaced 2. Need 6 white QR 155 degree heads in spare head box Building 2 1. Gauges shall be recalibrated or replaced 2. Need 6 white QR 155 degree heads in spare head box Building 3 1. Gauges shall be recalibrated or replaced 2. Need 6 white QR 155 degree heads in spare head box 3. Replace 5 painted heads in apartment 313. 4. Need a 5 year check valve inspection done. |