Case: T11FR01016

Parcel: 123052150


Addresses:

1900 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR01016

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
07/12/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Hydraulic cal plate missing for sprinkler system - shall replace missing plate
2. Water motor gong did not ring - Shall repair or replace
3. Inspectors test valve could not be use, because of floor drain not able to withstand water volume. - Shall repair floor drain or move piping to flow outside.