Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01016
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
07/12/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Hydraulic cal plate missing for sprinkler system - shall replace missing plate 2. Water motor gong did not ring - Shall repair or replace 3. Inspectors test valve could not be use, because of floor drain not able to withstand water volume. - Shall repair floor drain or move piping to flow outside. |