Case: T11FR01015

Parcel: 128090020


Addresses:

4700 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
08/02/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
07/08/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Leak at bottom of riser, below control valve. Leak caused by M.I.C. - Shall repair or replace pipe that is leaking.
2. Need a 5 year check valve inspection done.