Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR01012
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
07/06/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Water motor Gong failed - Shall repair or replace 2. 3 risers are pass due for their 5 year check valve inspection - Shall have inspections done. 3. 2 Audio/Visual signal devices failed - Shall repair or replace 4. Batteries load test at main panel failed - Shall repair or replace |