Case: T11FR00934

Parcel: 13409018E


Addresses:

8600 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T11FR00934

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/27/2011 INSP - FULL Correction Required Ace Hardware: 8600 E. Broadway Bl.

1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
-. Ceiling above the vacuum bags
- Near key making machine
- Under front desk counter

2. _____ 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a
3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.
- Currently there is a canopy that has been installed in the building that hampers the operation of the sprinkler system.

3. _____ 1028.6 Panic Hardware. Where panic hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted by the code.
- SE Exit

4. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
- Last 2007