Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T11FR00891
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2011 | INSP - FULL | Approved | all violations have been corrected. | |
04/22/2011 | INSP - FULL | Violation | 2006 IFC - 906.6 In areas which visual obstruction of fire extinguishers can not be completely avoided, means shall be provided to indicate the location of extinguishers. CORRECTION: You shall place a sign on your bar indicating location of extinguisher to the bar employees. 2006 IFC 1011.1 Exits shaqll be marked by approved and illumkinated exit signs visible from any direction of travel. CORRECTION: You shall place an illuminated exit sign over yuor SW bar exit. 2006 IFC 904.11.6.4 Certificate of commercial cooking hood and supression systems inspections shall be provided to the fire marshall upon completion. CORRECTION: You shall have a copy of your last building and commercial cooking supression system inspections provided to the fire inspector on or before May 13, 2011. This business has been referred to D.S.D. for a copy of their C of O. |