Case: T11FR00889

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00889

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2011 INSP - FULL Approved NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
04/22/2011 INSP - FULL Violation 1.) TFC 901.6 INSULATION PANELS HAVE FALLEN FROM CEILING AND ARE BLOCKING SPRINKLER COVERAGE IN 300 BASEMENT, NORTH.
04/22/2011 INSP - FULL Violation 2.) TFC 703.1.1 BY CENTRAL SUPPLY AIR HANDLER BY THE DOOR ON THE WEST END THERE ARE WALL PENETRATIONS THAT MUST BE SEALED.
04/22/2011 INSP - FULL Violation 3.) TFC 901.6 THE SPRINKLER RISER GAUGES IN G.I. LAB EQUIPMENT ROOM ARE MORE THAN 5 YEARS OLD.