Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2011 |
INSP - FULL |
|
Approved |
NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 04/22/2011 |
INSP - FULL |
|
Violation |
1.) TFC 901.6 INSULATION PANELS HAVE FALLEN FROM CEILING AND ARE BLOCKING SPRINKLER COVERAGE IN 300 BASEMENT, NORTH. |
| 04/22/2011 |
INSP - FULL |
|
Violation |
2.) TFC 703.1.1 BY CENTRAL SUPPLY AIR HANDLER BY THE DOOR ON THE WEST END THERE ARE WALL PENETRATIONS THAT MUST BE SEALED. |
| 04/22/2011 |
INSP - FULL |
|
Violation |
3.) TFC 901.6 THE SPRINKLER RISER GAUGES IN G.I. LAB EQUIPMENT ROOM ARE MORE THAN 5 YEARS OLD. |