Case: T11FR00881

Parcel: 13705006A


Addresses:

435 W IRVINGTON RD

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/21/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
04/21/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
04/21/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag
shall be affixed to the extinguisher with records of these activities