Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T11FR00840

Parcel: 129043150


Addresses:

2042 E 14TH ST


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T11FR00840

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/15/2011 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Abatement of electrical hazards.
Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box.

_____ Place electrical blanks in any open void spaces in your electrical panel

_____Replace non-approved wiring

605.5 Extension cords
Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ All extension cords shall be removed from permanent use