Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T11FR00814
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2011 | VIOL - MEANS OF EGRESS | Approved | All approved /closed | |
| 04/11/2011 | VIOL - MEANS OF EGRESS | Violation | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. |
|
| 04/11/2011 | VIOL - MEANS OF EGRESS | Violation | Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove bolt lock. |
|
| 04/11/2011 | VIOL - MEANS OF EGRESS | Violation | Security , locks, gates: 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _______ These signs shall be placed on the above-mentioned doors in an approved manor. |