Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2011 | INSP - FULL | Approved | All corrections have been made. | |
04/08/2011 | INSP - FULL | Violation | 2006 IFC 605.4 Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ECC Electrical Code shall be prohibited. 2001 IFC 605.6 Extension cords and flexible cords shall not be a substitute for permanent wiring. CORRECTION: You will remove any extension cords and multiplug adapters other than a UL listed power strip with oversurge protection. Each power strip MUST be plugged into its own outlet in the wall. 2006 IFC 703.1The required fire-resistance rating of fire-resitance-rated construction shall be maintained, and repaired, replaced, or restored when missing or damaged. CORRECTION: You will replace your missing ceiling tile in the storage room just above where your ladder is stored. 2006 IFC 605.3 A working space of not tess than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. CORRECTION: You will remove a shelf to allow clearance of your panel, or remove the metal shelving cart altogether. Maintain clearance around your electrical panel. |