Case: T11FR00790

Parcel: 12810082B

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T11FR00790

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2011 INSP - FULL Approved All violations have been corrected.
04/05/2011 INSP - FULL Violation 2006 IFC 904.11.6 Commercial Cooking Systems shall be operated and maintained in accordance with this code.
CORRECTION: You shall have your hood system repaired as required on your inspection report to ensure the ventillation system remains on during activation of the suppression system.

2006 IFC 901.4.1 Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code.
CORRECTION: You shall have the missing cap replaced on your FDC's ( fire department connections).

2006 IFC 504.2 Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters with a .75 inch wide and 6 inch high stroke on contrasting background.
CORRECTION: You will either render the doors to have a nonfunctional appearance, or you will post the sign in the doors that state they are blocked.