Inspection Status: Correction Required

Inspection History: VIOL - FIRE SERVICE FEATURES

Date Description Inspector Results Comments
04/05/2011 VIOL - FIRE SERVICE FEATURES Correction Required IFC 510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.

_____1. Post a sign stating " FIRE ALARM CONTROL PANEL INSIDE " on the outside of the employee entrance and on the door leading into the dock area from inside the building.