Case: T11FR00769

Parcel: 119040180


Addresses:

3541 S 12TH AV

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/01/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
04/01/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
___Replace filters for hood system.
04/01/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
***A K class extinguisher shall be installed according to this code.
04/01/2011 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag
shall be affixed to the extinguisher with records of these activities.