Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Scheduled
Inspection History: INSP - FULL
Case Number - T11FR00750
Inspection Description - INSP - FULL
Inspection Status - Scheduled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2011 | INSP - FULL | Scheduled | Plans submitted and approved and permit granted (on 5/11/11) to drop 3 sprinkler heads in freezer. - T11BU00625 - | |
03/30/2011 | INSP - FULL | Violation | 1. 2006 IFC 605.6 Approved covers shall be provided for all switch boxes. CORRECTION: A) You shall place a blank in the open circuit on your 'Panel A' electrical breaker box. B) You shall secure the cover to your electrical panel in the drinks room just SW of the main entrance. 2. 2006 IFC 906.6 Portable fire extinguishers shall not be obstructed or obscured from view. CORRECTION: You shall remove all storage ( bread carts, shelves, boxes, etc. ) that are blocking the view and full access to your fire extinguisher next to your Bread Oven in the kitchen. 3. 2006 IFC 901.4 Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled, or added to. CORRECTION: You will contact your sprinkler installation company and have them design and submit plans for your sprinkler system to be extended to the 'Polar King' freezer that has been added. These plans will need to be approved before the work begins. 4. 2006 IFC 903.3.3 Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. CORRECTION: The security gate that has been added to protect your liquor in the walk in refrigerator is blocking the water distribution pattern of the sprinkler head designed to cover that area. You shall lower the security fence below the sprinkler head so as not to interfere with the spray pattern. |