Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/30/2011 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____1. Remove the cube adapter located by the south window.
NOTE: Replace it with a fused power-strip.
03/30/2011 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

_____1. All open spaces in the electrical panel located in the kitchen shall have an approved cover.