Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T11FR00730
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2011 | INSP - FULL | Approved | All violations have been corrected. | |
03/29/2011 | INSP - FULL | Violation | 1. 2006 IFC 1011.1 Where there are two or more required exits, the exits shall be marked with illuminated exit signs. CORRECTION: You shall provide exit signs over your front and rear exit. 2. 2006 IFC 1008.1.8.3 A key locking device is permitted on the main exterior exit door where a sign over the door reads, "This door to remain unlocked while the building is occupied." CORRECTION: You shall provide replace the key locking cylinder on your rear exit with a thumb turn bolt. 3. 2006 IFC 308.3.2 Open flame device holders will return to the upright position after being tilted to a 45 degree angle and where a piece of tissue paper is placed on top of the holder it will not ignite in less than 10 seconds. CORRECTION: You shall cease burning candles until the proper holder is in place. 4. 2006 IFC 906.1 Fire extinguishers shall be tested/ inspected yearly. CORRECTION: You shall have your fire extinguisher tested and tagged by a qualified individual or company. 5. 2006 IFC 605.6 Approved covers shall be provided for outlets. CORRECTION: Secure your loose outlet cover on the SW wall of the showroom behind the bed display. |