Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T11FR00719
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2011 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
03/28/2011 | INSP - FULL | Violation | 1.) TFC 906.1 REPLACE MISSING LIGHT COVER IN E.D. BY EXAM ROOM #29. | |
03/28/2011 | INSP - FULL | Violation | 2.) TFC 703.1.1 SEAL WALL PENETRATION IN MEDICAL STORAGE ROOM BY ANNEX IN E.D. | |
03/28/2011 | INSP - FULL | Violation | 3.) TFC 703.1.1 SEAL WALL PENETRATION NEAR FLOOR BY E.R. EXAM ROOM #37. | |
03/28/2011 | INSP - FULL | Violation | 4.) TFC 703.1.1 SEAL WALL PENETRATION BEHIND DOOR IN FAMILY COUNSELING ROOM. | |
03/28/2011 | INSP - FULL | Violation | 5.) TFC 703.1.1 SEAL WALL PENETRATION BEHIND DOOR IN E.R. RESPIRATORY CARE CLOSET. | |
03/28/2011 | INSP - FULL | Violation | 6.) TFC 703.1.1 SEAL WALL PENETRATION BEHIND DOOR IN SOILED UTILITY BY STAFF LOUNGE. | |
03/28/2011 | INSP - FULL | Violation | 7.) TFC 906.1 CEILING TILES MUST BE KEPT IN PLACE IN LIFE NET HALLWAY ON 2ND FLOOR. | |
03/28/2011 | INSP - FULL | Violation | 8.) TFC 906.1 SPRINKLER HEADS IN RESTROOMS IN LIFENET LIVING QUARTERS HAVE BEEN PAINTED AND NEED TO BE REPLACED. | |
03/28/2011 | INSP - FULL | Violation | 9.) TFC 605.5 THE EXTENSION CORD IN PERMANENT USE IN N.E OFFICE OF LIFENET IS NOT PERMITTED. |