Case: T11FR00691

Parcel: 107141960


Addresses:

2552 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - COMPRESSED GASES

Case Number - T11FR00691

Inspection Description - VIOL - COMPRESSED GASES

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/23/2011 VIOL - COMPRESSED GASES Correction Required IFC 3003.5.2 Physical protection. Compressed gas containers,
cylinders, tanks and systems which could be exposed to
physical damage shall be protected. Guard posts or other
approved means shall be provided to protect compressed
gas containers, cylinders, tanks and systems indoors and
outdoors from vehicular damage and shall comply with Section
312.

_____1. All propane cylinders and the tank on the east side of the building shall be protected by Guard posts or other approved means and shall meet the following requirements:

312.2 Posts. Guard posts shall comply with all of the following
requirements:
1. Constructed of steel not less than 4 inches (102 mm) in
diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on
center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing
of not less than a 15-inch (381 mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm)
above ground.
5. Located not less than 3 feet (914 mm) from the protected
object.

312.3 Other barriers. Physical barriers shall be a minimum of
36 inches (914 mm) in height and shall resist a force of 12,000
pounds (53 375 N) applied 36 inches (914 mm) above the adjacent
ground surface.
03/23/2011 VIOL - COMPRESSED GASES Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.

_____1. All LP-gas and Oxygen cylinders shall be properly secured with a chain or strap to prevent them from falling.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.
All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg