Case: T11FR00687

Parcel: 140411260

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR00687

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2012 VIOL - FIRE PROTECTION SYSTEMS Approved Sprinkler deficiencies on pre-citation corrected
03/23/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Replace out dated gauges - Shall re-calibrate or replace gauges.
2. Piping to lower gauge corroded and plugged - Shall repair or replace piping.
3. Overhead storage has no coverage below - shall correct sprinkler coverage. Note: you will need to have an approved plan and permit before work is done.