Case: T11FR00683

Parcel: 134270080


Addresses:

400 S BROADWAY PL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR00683

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/12/2011 VIOL - FIRE PROTECTION SYSTEMS Approved
03/23/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Riser #1 Flow switches failed for 3rd floor common area and 2nd floor I wing. - Shall repair or replace flow switches.
2. Riser #2 Flow switches failed for G wing 1st Floor, F wing 1st floor, H wing 2nd and 3rd floor. - Shall repair or replace flow switches.
3. Riser #3 Flow switch at wing B 1st floor stays stuck open when tested. - Shall repair or replace switch.
4. Riser #3 ITV shut off valve leaks when open B bldg 2nd floor - Shall repair or replace valve.