Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T11FR00683
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 03/23/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Riser #1 Flow switches failed for 3rd floor common area and 2nd floor I wing. - Shall repair or replace flow switches. 2. Riser #2 Flow switches failed for G wing 1st Floor, F wing 1st floor, H wing 2nd and 3rd floor. - Shall repair or replace flow switches. 3. Riser #3 Flow switch at wing B 1st floor stays stuck open when tested. - Shall repair or replace switch. 4. Riser #3 ITV shut off valve leaks when open B bldg 2nd floor - Shall repair or replace valve. |